Straight cast resin cable joints are suitable for plastic and paper insulated LV cables. These joints are suitable for use in multiple applications (i.e. power, telecoms, signalisation). The range is available complete with armour earth kit.
Joint Data | |
Type Tested | DIN EN 50393:2006-11 |
Temperature Range | -10°C to +120°C |
Voltage | 600/1000 volts |
Armour Earth Kit | Insulated Braid and CF Springs |
The P2654 Polyurethane Resin is a high quality product, tested to >20kV/mm, with a performance temperature range of -25°C to +120°C. The P2654 has a Gel Time of 14 minutes, and a shelf life of 24 months from date of manufacture.
Resin Data | |
Resin Type | Polyurethane |
Resin Type Test | IEC 60455-3-8:2013 |
Resin Hardness | Shore D (41) EN ISO 868 |
Diaelectric Strength | 20kV/mm |
Colour | Black |
Mixing Time | 2 Minutes |
Tensile Strength | MPa 7.07 EN ISO 527 |
Elongation at break | 40% EN ISO 527 |
Note: Splice/Mechanical Connectors are not included but are available for supply separately.