Medium Voltage AWA LSZH Copper BS7835

Download Data Sheet

BS7835-compliant medium voltage armoured cables, featuring stranded copper conductors, are ideal for outdoor use, direct burial, and cable ducting. They’re designed for medium voltage power transmission in various applications.

Download Here

BS7835-compliant medium voltage armoured cables, featuring stranded copper conductors, are ideal for outdoor use, direct burial, and cable ducting. They're designed for medium voltage power transmission in various applications. 

Conductor

Plain Copper

Stranding

Class 2

Insulation

XLPE

Metallicscreen

Plain Copper Taped Screen

Bedding

LSZH

Armour

Aluminium Wire Armour

Outersheath

LSZH

Colour

Red

Voltage

6.35/11kV

Bendingradius

15 x Overall Diameter

Temperature

90°C

Standards

BS7835, BS EN 60332-1-2.

BATT Part No Size mm RT of insulation mm Nominal diameter over CTS mm RT of bedding mm Diameter over Bedding mm Diameter of armour wires mm Diameter over Armour mm Approx overall Diameter mm Weight
56182 70 3.4 20.2 1.2 22.9 1.6 26.4 29 1500
56222 95 3.4 22.3 1.2 25 1.6 28.5 31 1800
56387 120 3.4 23.5 1.2 26.2 1.6 30.5 32.5 2100
56600 150 3.4 25 1.5 27.7 2 32 35 2400
56034 185 3.4 26.8 1.2 29.5 2 33.8 36.5 2800
56368 240 3.4 29.1 1.2 31.8 2 36.1 39 3400
56229 300 3.4 31.6 1.2 34.3 2 38.6 41 4100
56168 400 3.4 34.4 1.2 37.1 2 42.4 45 5000
56329 500 3.4 37.6 1.3 40.5 2.5 45.8 49.5 6300
630 630 3.4 41.5 1.4 44.6 2.5 49.9 54 7800
Batt Part No. Core Size Colour/Reference
56182 1 70 Red
56222 1 95 Red
56387 1 120 Red
56600 1 50 Red
56034 1 85 Red
56368 1 240 Red
56229 1 300 Red
56168 1 400 Red
56329 1 500 Red
56035 1 630 Red

The information in this datasheet is for guidance only and subject to change without liability. Images provided are representations; actual cable dimensions may vary due to manufacturing tolerances.