Medium Voltage AWA PVC Copper BS6622

Download Data Sheet

BS6622-compliant medium voltage armoured cables, featuring stranded copper conductors, are ideal for outdoor use, direct burial, and cable ducting. They’re designed for medium voltage power transmission in various applications.

Download Here

BS6622-compliant medium voltage armoured cables, featuring stranded copper conductors, are ideal for outdoor use, direct burial, and cable ducting. They're designed for medium voltage power transmission in various applications.

Conductor

Plain Copper

Stranding

Class 2

Insulation

XLPE

Metallicscreen

Plain Copper Taped Screen

Bedding

PVC

Armour

Aluminium Wire Armour

Outersheath

PVC

Colour

Red

Voltage

6.35/11kV

Bendingradius

15 x Overall Diameter

Temperature

90°C

Standards

BS6622, BS EN 60332-1-2.

Nominal cross sectional area of conductor RT of Insulation Nominal Diameter over copper screen RT of Bedding mm Diameter over bedding Diameter of armour wire Diameter of armour Approx overall diameter mm Weight
95 3.4 22.3 1.2 25 1.6 28.5 32.8 1850
120 3.4 23.5 1.2 26.2 1.6 30.5 34.8 2160
150 3.4 25 1.2 27.7 2 32 36.5 2590
185 3.4 26.8 1.2 29.5 2 33.8 38.3 2980
240 3.4 29.1 1.2 31.8 2 36.1 36.1 3640
300 3.4 31.6 1.2 34.3 2 38.6 38.6 4330
400 3.4 34.4 1.2 37.1 2.5 42.4 42.4. 5480
500 3.4 37.6 1.3 40.5 2.5 45.8 45.8 6550
630 3.4 41.5 1.4 44.6 2.5 49.9 49.9 8080

The information in this datasheet is for guidance only and subject to change without liability. Images provided are representations; actual cable dimensions may vary due to manufacturing tolerances.