Solid Aluminium SWA Power Cable Generally to BS5467(where applicable)

Download Data Sheet

Power cable suitable for power networks, direct burial, outdoors, indoors and in cable
ducts

Download Here

Power cable suitable for power networks, direct burial, outdoors, indoors and in cable ducts

Conductor

Aluminium

Stranding

Class 1

Insulation

XLPE

Armour

Steel Wire Armour

Outersheath

PVC

Colour

Black

Voltage

0.6/1kV

Ratingtables

4H4A, 4H4B

Identification

4 Core: Brown, Black, Grey, Blue

Bendingradius

Overall Bending Radius 10x

Temperature

Maximum 90°C, minimum bending 0°C

Standards

Generally to BS5467(where applicable)

BATT Part No Cores Nominal cross sectional area of conductor RT of insulation Diameter over core mm2 RT of bedding Diameter of armour wire mm2 Diameter over armour mm2 Approx overall diameter Weight
56201 4 35 0.9 17.9 1.0 1.6 23.3 27 1430
56202 4 50 1.0 20.7 1.0 1.6 26.1 30 1725
56203 4 70 1.1 24.1 1.2 2.0 30.9 35.3 2525
56613 4 95 1.1 27.6 1.2 2.0 34.4 37.7 2800
56205 4 120 1.2 31.0 1.4 2.5 39.2 44 3950
56206 4 150 1.4 34.7 1..4 2.5 42.9 47. 4500
56644 4 185 1.6 38.8 1.4 2.5 47.2 52.7 5164
56208 4 240 1.7 44.0 1.6 2.5 52.8 58.5 6400
Batt Part No. Core Size Colour/Reference
56200 4 25 Black
56201 4 35 Black
56202 4 50 Black
56203 4 70 Black
56613 4 95 Black
56205 4 120 Black
56206 4 150 Black
56644 4 185 Black

The information in this datasheet is for guidance only and subject to change without liability. Images provided are representations; actual cable dimensions may vary due to manufacturing tolerances.

Choose your accessories